Supply |
---|
Connection | terminals 11+, 12- terminals 8+, 9- |
Rated voltage | 20 ... 30 V DC The maximum rated operating voltage of the devices plugged onto the Power Rail must not be exceeded. |
Fusing | 5 AT/250 V AC recommended maximum utilization of the fuse: 80 % |
Power dissipation | ≤ 2.4 W |
Output |
---|
Connection | Power Rail |
Output rated operating current | max. 4 A |
Output voltage | Ui ≥ rated voltage Ur = Ui - 0.6 V |
Fault signal | relay output: NO contact |
Contact loading | 30 V AC/ 2 A / cos φ ≥ 0.7 ; 40 V DC/ 2 A |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
Indicators/settings |
---|
Display elements | LEDs |
Control elements | DIP switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity |
---|
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
---|
Electromagnetic compatibility | NE 21:2006 |
Degree of protection | IEC 60529:2001 |
Ambient conditions |
---|
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
---|
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 100 g |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
---|
Certificate | TüV 00 ATEX 1618 X |
| Marking | II 3G Ex nA nC IIC T4 |
Directive conformity | |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-15:2010 |
International approvals |
---|
FM approval | |
| Control drawing | 116-0160 |
UL approval | E106378 |
CSA approval | CoC 1051840 |
IECEx approval | |
| IECEx certificate | IECEx UL 16.0051X |
| IECEx marking | Ex nA nC IIC T4 Gc |